System X20. I/O Unit 4 Digital outputs. 24VDC Source
X20DO4332-1
I/O module | 4 digital outputs 24 VDC for 3-wire connections |
B&R ID code | 0x1B9C |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Outputs | Yes, using LED status indicator and software (output error status) |
Power consumption | |
Bus | 0.16 W |
Internal I/O | 0.49 W |
Additional power dissipation caused by actuators (resistive) [W] | +1.6 (Rev. <H0: +2.24) |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial control equipment |
HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
EAC | Yes |
KC | Yes |
Variant | Current-sourcing FET |
Nominal voltage | 24 VDC |
Switching voltage | 24 VDC -15% / +20% |
Nominal output current | 2 A |
Total nominal current | 8 A (Rev. <H0: 4 A) |
Connection type | 3-wire connections |
Output circuit | Source |
Output protection | Thermal shutdown in the event of overcurrent or short circuit (see value «Short-circuit peak current») Internal freewheeling diode for switching inductive loads (see section «Switching inductive loads») |
Actuator power supply | 0.5 A in total for output-independent actuator power supply |
Diagnostic status | Output monitoring with 10 ms delay |
Leakage current when the output is switched off | 5 µA |
RDS(on) | 100 mΩ (Rev. <H0: 140 mΩ) |
Peak short-circuit current | <4 A (Rev. <H0: <12 A) |
Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 10 ms (depends on the module temperature) |
Switching delay | |
0 → 1 | <300 µs |
1 → 0 | <300 µs |
Switching frequency | |
Resistive load | Max. 500 Hz |
Inductive load | See section «Switching inductive loads». |
Braking voltage when switching off inductive loads | Typ. 50 VDC |
Insulation voltage between channel and bus | 500 Veff |
Additional functions | Outputs can be connected in parallel to increase the output current. |
Voltage | Module power supply minus voltage drop for short-circuit protection |
Voltage drop for short-circuit protection at 500 mA | Max. 2 V |
Short-circuit proof | Yes |
Power consumption | |
Actuator power supply | Max. 12 W |
Electrical isolation | Channel isolated from bus Channel not isolated from channel and I/O power supply |
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section «Derating». |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2mm |
The module is equipped with 4 outputs for 3-wire connections. The nominal output current is 2 A.
Somos Wartung Automation, Lider en equipamientos B&R, repuestos y service para la automatizacion en Argentina hace 23 anos.
Atendemos Industrias farmacéuticas, alimenticias, procesos, laboratorios, metalmecanica.
Consulte por toda la linea de productos B&R, somos Service Provider Wartung Automation Argentina.
Mas información acerca de este producto?
Weight | 05 kg |
---|---|
Dimensions | 5,7 × 2,5 × 9,5 cm |