General:
Item H3BA-N H3BA-N8H
Operating mode A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval
G: Signal ON/OFF-delay
J: One-shot A: ON-delay
H: ON-delay with instantaneous output contact
Pin type 11-pin 8-pin
Input type No-voltage input —
Output type DPDT (time-limit) SPDT (time-limit) and switchable SPDT (time-limit <—>
instantaneous)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508 *1, CSA C22.2 No.14, LR, CCC: GB/T 14048.5 *2
Conforms to EN61812-1 (Pollution degree 2/Overvoltage category III)
EMC (EMI) EN61812-1
Radiated Emissions: EN 55011 class A
Emission AC Mains: EN 55011 class A
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge
Radiated Radio-Frequency EN 61000-4-3: 10 V/m (80 MHz to 1 GHz AM modulation)
Electromagnetic Field Immunity: 3 V/m (1.4 GHz to 2 GHz AM modulation), 1 V/m (2 GHz to 2.7
GHz AM modulation), 10 V/m (900 MHz Pulse modulation)
Conducted disturbances: EN 61000-4-6: 10 V (0.15 MHz to 80 MHz)
Burst Immunity: EN 61000-4-4: 2 kV power line, 2 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode
Voltage dips: EN 61000-4-11
Voltage interruptions: EN 61000-4-11
*1.Surrounding air temperature: 0°C to 40°C
*2.CCC certification requirements
Recommended fuse 0216005 (250 VAC, 5 A) manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 1.5 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.) 4 kV (at 240 VAC)
Conditional short-circuit current 1,000 A
Time Ranges
Time unit sec × 10 s min × 10 m hrs × 10 h
Full scale setting
1.2 Set time 0.05 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12
3 0.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120
30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300
Ratings
Item H3BA-N H3BA-N8H
Rated supply voltage *1 *2 110 VAC (50/60 Hz), 220 VAC (50/60 Hz), 24 VDC
Operating voltage range *3 85% to 110% of rated supply voltage
Power reset Minimum power-opening time: 0.1 s
No-voltage input ON impedance: 1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance: 200 kΩ min.
Power consumption 110 VAC: Approx. 4.6 VA (1.5 W)
220 VAC: Approx. 7.6 VA (1.3 W)
24 VDC: Approx. 0.6 W 110 VAC: Approx. 3.6 VA (1.6 W)
220 VAC: Approx. 7.8 VA (1.9 W)
24 VDC: Approx. 0.9 W
Control outputs Contact: 5 A at 250 VAC, resistance load (cosφ = 1)
*1. DC ripple rate: 20% max.
*2. Models other than 24-VDC H3BA-N models cause an inrush current. Pay careful attention when attempting to turn on
power to such models with non-contact output from a device such as a sensor.
*3. 90% or higher if the Timer is used continuously at a high ambient temperature.
Characteristics
Item H3BA-N H3BA-N8H
Accuracy of operating time ±0.3% FS max. (±0.3%±10 ms in a range of 1.2 s)
Setting error ±5% FS ±0.05 s max.
Reset time Min. power-opening time: 0.1 s max.
Min. pulse-input time: 50 ms
Influence of voltage ±0.5% FS max. (±0.5%±10 ms in a range of 1.2 s)
Influence of temperature ±2% FS max. (±2%±10 ms in a range of 1.2 s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and exposed non-
current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between control output terminals and operating circuit
1,000 VAC, 50/60 Hz for 1 min between contacts not located next to each other (750
VAC for H3BA-N8H)
Impulse withstand voltage 1 kV (between power terminals)
2 kV (between current-carrying terminal and exposed non-current-carrying metal parts,
1.5 kV for 24-VDC models)
Noise immunity AC models:
±1.5 kV (between power terminals), and ±600 V (between input terminals),
square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
DC models:
±480 V (between power terminals), and ±600 V (between input terminals),
square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Malfunction: 4 kV
Destruction: 8 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in three directions
Shock resistance Destruction: 1,000 m/s2 (approx. 100G) each in three directions
Malfunction: 100 m/s2 (approx. 10G) each in three directions
Ambient temperature Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10 million operations min.
(under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at
250 VAC, resistive load at 1,800
operations/h) Mechanical: 10 million operations min.
(under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at
250 VAC, resistive load at 360
operations/h)
Case color Light gray (Munsell 5Y7/1)
Enclosure ratings IEC: IP40 (panel surface)
Weight Approx. 95 g
Note: For setting the time-limit of the Timer to a cycle of less than 3 seconds or applying the forced reset, use the H3BA-N
in mode D (signal OFF-delay).
Mas Información?