X20, Modulo de Fuente de Alimentación para controil de BUS alimentación entradas y salidas.
X20PS9400
DESCRIPTION:
The supply module is used together with an X20 bus controller. It is equipped with a feed for the bus controller, the X2X Link and the internal I/O supply.
Power supply module | 24 VDC supply module for bus controller, X2X Link power supply and I/O |
Interfaces | 1x RS232 service interface |
B&R ID code | 0x1F8C |
Status indicators | Overload, operating status, module status, RS232 |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
RS232 data transfer | Yes, using LED status indicator |
Overload | Yes, using LED status indicator and software |
Power consumption for X2X Link power supply | 1.42 W |
Power consumption | |
Internal I/O | 0.6 W |
Additional power dissipation caused by actuators (resistive) [W] | – |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial control equipment |
HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 to 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV | EC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck |
EAC | Yes |
KC | Yes |
Input voltage | 24 VDC -15% / +20% |
Input current | Max. 0.7 A |
Fuse | Integrated, cannot be replaced |
Reverse polarity protection | Yes |
Nominal output power | 7 W |
Parallel connection | Yes |
Redundant operation | Yes |
Overload characteristics | Short-circuit proof, temporary overload |
Input voltage | 24 VDC -15% / +20% |
Fuse | Required line fuse: Max. 10 A, slow-blow |
Reverse polarity protection | No |
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Service interface | |
Signal | RS232 |
Variant | Connection made using 12-pin terminal block X20TB12 |
Max. transfer rate | 115.2 kbit/s |
Electrical isolation |
BC/X2X Link supply isolated from BC/X2X Link power supply
I/O supply not isolated from I/O power supply, and RS232 not isolated from bus
|
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section «Derating». |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Note | Order 1x terminal block X20TB12 separately. Order 1x bus base X20BB8x separately. |
Pitch | 12.5+0.2mm |