ReLy. SAFETY RELAYS. Type of output. PNP semiconductors, short-circuit protected. Output voltage. ≥ Vs – 3 V. Test pulse width. 2 ms.
ReLy safety relay for sensors with potential-free outputs.
Electrical data Operating data
Safety inputs
RLY3-EMSS300 | ReLy
SAFETY RELAYS
Voltage supply |
PELV or SELV |
Supply voltage VS |
24 V DC (16.8 V … 30 V) |
Residual ripple |
≤ 2.4 V |
Power consumption |
≤ 2.5 W (DC) |
Number |
2 |
Input voltage |
HIGH 24 V DC (11 V … 30 V) LOW 0 V DC (–3 V … 5 V)
Input current |
4 mA … 6 mA |
Activation time tolerance between the two start buttons |
≤3 s |
Reset pushbutton or external device monitoring (EDM) input
Number |
1 |
Input voltage |
Enabling current paths
Application diagnostic outputs
Test pulse outputs
2023-02-23 12:52:20 | Product data sheet Subject to change without notice
HIGH ≥ Vs – 3 V LOW ≤ 3 V
HIGH 24 V DC (11 V … 30 V) LOW 0 V DC (–3 V … 5 V)
Input current |
4 mA … 6 mA |
Response time |
12 ms |
Number |
3 |
Type of output |
N/O contacts, positively guided |
Contact material |
Silver alloy, gold flashed |
Switching voltage |
10 V AC … 230 V AC 10 V DC … 230 V DC |
Switching current |
10 mA … 6 A |
Total current |
12 A |
Mechanical life |
1 x 107 switching cycles |
Overvoltage category |
III (EN 60664-1) |
Rated impulse withstand voltage Uimp |
6 kV (EN 60664-1) |
Number |
2 |
Type of output |
Push-pull semiconductor output, short-circuit protected |
Output voltage |
Input current (NPN) |
≤ 15 mA |
Output current (PNP) |
≤ 120 mA |
Number |
3 |
Somos Wartung Automation, Lider en Sick , repuestos para la automatizacion en Argentina hace 23 anos.
Mas informacion?
Weight | 0,2 kg |
---|---|
Dimensions | 8,5 × 1,8 × 12,4 cm |