Pepperl+Fuchs Factory Automation
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 75 mm | |
| Installation | non-flush | |
| Output polarity | DC | |
| Assured operating distance | 0 … 55 mm | |
| Reduction factor rAl | 1 | |
| Reduction factor rCu | 1 | |
| Reduction factor r304 | 1 | |
| Reduction factor rSt37 | 1 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 … 30 V DC | |
| Switching frequency | 0 … 50 Hz | |
| Hysteresis | typ. 3 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | ≤ 3 V | |
| Temperature drift | ± 10 % at 0 … 50 °C (32 … 122 °F) ± 20 % at -25 … 0 °C (-13 … 32 °F) and 50 … 70 °C (122 … 158 °F) |
|
| Rated insulation voltage | 50 V | |
| Operating current | 0 … 200 mA | |
| Off-state current | 0 … 0.5 mA | |
| No-load supply current | ≤ 20 mA | |
| Time delay before availability | ≤ 300 ms | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 824 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 … 70 °C (-13 … 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector plug M12 x 1 , 4-pin | |
| Housing material | PBT/metal | |
| Sensing face | PBT | |
| Housing base | metal | |
| Degree of protection | IP68 | |
| Dimensions | 8 × 5,5 × 8 cm |
|---|