Technical data
Communication | PROFIBUS |
Number of fieldbus nodes on master (max.) | 96 |
Number of I/O points | 6,000 |
Baud rate | 9.6/12 MBd |
Bus segment length (max.) | 1200 m |
Transmission medium | Cu cable per EN 50170 |
Transmission time | typ. 1 ms (10 couplers; each 32 digital I/O and 12 Mbaud) max. 3.3 ms |
Number of modules per node (max.) | 63 |
Number of modules without a bus extension (max.) | 63 |
Input and output process image (fieldbus) max. | 244 bytes/244 bytes |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
Current consumption (5 V system supply) | 200mA |
Total current (system supply) | 1,800mA |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
Input current (typ.) at nominal load (24 V) | 500mA |
Power supply efficiency (typ.) at nominal load (24 V) | 87% |
Isolation | 500 VDC system/field |
Number of outgoing power jumper contacts | 3 |
Current carrying capacity (power jumper contacts) | 10A |
Standard | EN 50170 |
Mas informacion?
Weight | 0,045 kg |
---|---|
Dimensions | 6,5 × 5,1 × 10 cm |