I/O module | 8 inputs in 2 groups for thermocouples |
Status indicators | Converter function, measurement time, temperature sensor per group |
Diagnostics | |
Module status | Yes, using software |
Converter | Yes, using LED status indicator |
Power consumption | |
24 VDC | 4.75 W |
5 VDC | 1.25 W |
Total | 6.0 W |
Electrical isolation | |
Group – Group | No |
Channel – Channel | No |
Channel – PLC | Yes |
Certifications | |
CE | Yes |
UKCA | Yes |
UL | cULus E115267 Industrial control equipment |
EAC | Yes |
Input | Thermocouple |
Digital converter resolution | Internal >14-bit (23841 internal ADC converter values at 20 ms) |
Conversion time | |
16.67 ms measurement time | 116.68 ms including internal terminal temperature compensation |
20 ms measurement time | 130 ms including internal terminal temperature compensation |
Output format | INT |
Measurement range | |
Sensor temperature | |
FeCuNi: Type J | -200 to 950°C |
FeCuNi: Type L | -200 to 900°C |
NiCrNi: Type K | -200 to 1300°C |
Raw value | -15 to +55 mV |
Terminal temperature compensation | Can be both internal and external |
Basic accuracy | |
Type J: Fe-CuNi | ±0.5% at 25°C |
Type L | ±0.5% at 25°C |
Type K: NiCr-Ni | ±0.8% at 25°C |
Terminal temperature compensation | |
External | -100 to 200°C |
Internal | -20 to 80°C |
Input protection | Protection against wiring with supply voltage |
Somos representantes de B&R en Argentina, hacemos service y reparaciones de PLC X20, system, B&R, Buenos Aires,
Su consulta no molesta.
Mas informacion?
>>>3at6606
Weight | 0,230 kg |
---|