General information
Status indicators |
Converter function, start pulse for software timing |
Diagnostics |
|
Module status |
Yes, using software |
Converter |
Yes, using LED status indicator |
Power consumption |
|
24 VDC |
3.5 W |
5 VDC |
1.0 W |
Total |
4.5 W |
Electrical isolation |
|
Channel – Channel |
No |
Channel – PLC |
Yes |
Certifications |
|
CE |
Yes |
UKCA |
Yes |
UL |
cULus E115267
Industrial control equipment |
EAC |
Yes |
Analog inputs
Input |
0 to 20 mA |
Input type |
Differential input |
Digital converter resolution |
12-bit |
Conversion time |
<1 ms for all inputs, <1.5 ms with averaging enabled |
Output format |
INT |
Load |
50 Ω |
Operating modes |
Cyclic measurement with optional averaging, direct software timing, software timing with time specification (2 – 65.535 ms) |
Basic accuracy |
±0.1% at 25°C |