El Allen-Bradley 1794-AENTR es un adaptador de comunicación Flex I/O. Este adaptador es un dispositivo montado en riel DIN, que cuenta con dos (2) puertos de comunicación Ethernet, que se utilizan para conectar el bastidor Flex I/O a un controlador central habilitado para Ethernet. Admite una velocidad de comunicación de 10/100 Mbps con un requisito de voltaje de entrada de 19,2 – 31,2 VCC. Admite la instalación de hasta ocho (8) módulos Flex I/O.
Technical Specifications for 1794-AENTR
Manufacturer | Rockwell Automation |
Power Dissipation | 6.1 W @ 19.2V DC |
Power Consumption: | 500 mA 400 mA @ 24V DC |
Operating Shock: | 30 g peak acceleration, 11(+1)ms pulse width |
Vibration: | Tested 5 g @ 10-500Hz per IEC 68-2-6 |
Storage Temperature: | -40 to 85 C (-40 to 185 F) |
Operating Temperature: | 0 to 55 C (32 to 131 F) |
Wire Size: | 0.34…2.5 mm2 (22…12 AWG) stranded copper wire rated at 75 °C (167 °F) or higher, 1.2 mm (3/64 in.) insulation max |
Ethernet cable: | RJ45 Cat.5 |
Mounting: | DIN Rail |
Indicators: | Mod Status; Network Status; Link1 Status; Link2 Status |
Data Transfer speed: | 10 to 100 Mbps |
Supported topologies: | Linear |
Supported Protocol: | Ethernet I/P |
Communication Port: | Two (2) RJ45 |
Product Description: | Redundant Ethernet Adapter Module |
Brand | Allen-Bradley |
Thermal Dissipation | 20.8 BTU/hr @ 24V DC |
Part Number/Catalog No. | 1794-AENTR |
Product Type | Flex I/O Dual Port Ethernet/IP Adapter Module |
I/O Capacity | 8 Modules |
Communication Rate | 10/100 Mbps |
Input Voltage Range nom. | 19.2 to 31.2 Volts DC |
Input Voltage nominal | 24 Volts DC |
Inrush Current | 18 Amps for 2 milliseconds |
Enclosure Type Rating | None (open-style) |
Isolation Voltage | 50 Volts Continuous |
Flexbus Current | 640 mA at 5 Volts DC maximum |
UPC | 10612598350145 |
Service, Ingenieria, Comunicaciones, Operaciones en campo, Allen Bradley, Service Argentina.
Mas Informacion??794-TD014
Weight | 0,180 kg |
---|---|
Dimensions | 8,7 × 8,7 × 9,2 cm |