Number of analog outputs |
2 |
Total number of channels (module) |
2 |
Signal type |
Current |
Signal type (current) |
4 … 20 mADC |
Actuator connection |
2 x (2-wire) |
Resolution [bit] |
12Bit |
Data width |
2 x 16-bit data; 2 x 8-bit control/status (optional) |
Load impedance (current output) |
≤ 600 Ω |
Conversion time (typ.) |
2ms |
Measurement error (reference temperature) |
25°C |
Measurement error, deviation (max.) from the upper-range value |
0.1% |
Temperature error (max.) of the upper-range value |
0.015%/K |
Output error, deviation (max.) of the upper-range value |
0.1% |
Temperature error (max.) of the output range value |
0.015%/K |
Linearity |
±10 µA |
Supply voltage (system) |
5 VDC; via data contacts |
Current consumption (5 V system supply) |
70mA |
Supply voltage (field) |
24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact) |
Isolation |
500 V system/field |
Indicators |
LED (A, C) green: Function AO 1, AO 2 |
Number of incoming power jumper contacts |
2 |
Number of outgoing power jumper contacts |
2 |